UPS Online Sinewave

RN2100C

2000VA / 1800W | 110 ~ 300Vac (depend on load percentage)

ICA UPS RN 2100 C Capacity 2000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Key Features

Reliable Power for Various Applications

Auto Charging at Off Mode

Auto-Restart Function

Cost Effective Solution

Specification

Capacity

:

2000VA / 1800W
AC Input Voltage

:

110 ~ 300Vac (depend on load percentage)
Inverter Output Voltage

:

200 / 208 / 220 / 230 / 240Vac
Inverter Output Waveform

:

Pure sinewave
Inverter Output Efficiency

:

>89%
Transfer Time

:

Utility to Battery: 0ms; Utility to Bypass: <4ms
Dimension (L x W x H)

:

440 x 86.5 x 435mm (2U)
Net Weight

:

19.6Kg
INPUT

:

Rated voltage

:

200 / 208 / 220 / 230 / 240Vac
Frequency range

:

40 ~ 70Hz (auto detect)
Power factor

:

≥0.99
Bypass voltage range

:

Bypass high voltage point Setting in LCD from 230Vac to 264Vac (Default: 264Vac)
Bypass low voltage point Setting in LCD from 170Vac to 220Vac (Default: 170Vac)
Generator input

:

Support
BATTERY

:

Battery voltage

:

48Vdc
Typical recharge time

:

4 hours (to 90% of full capacity)
Backup time

:

Estimated remaining time displayed on the LCD
Charging current (max.)

:

1A
OUTPUT

:

Power factor

:

0.9
Voltage regulation

:

±1%
Frequency line mode

:

45 ~ 55Hz (for 50Hz) or 55 ~ 65Hz (for 60Hz)
Frequency bat. mode

:

50 / 60 (±0.01%)Hz
Crest factor

:

3 : 1
Harmonic distortion (THDv)

:

≤3% with linear load; ≤6% with non-linear load
SYSTEM

:

Overload (Line Mode)

:

Load ≤110%: last 10min; ≤130%: last 1min; ≤150%: last 5S; >150% turn to bypass mode (1 ~ 3kvA)
Load ≤110%: last 60min; ≤125%: last 10min; ≤150%: last 1S; >150% turn to bypass mode (6 ~ 10kvA)
Short circuit

:

Hold whole system
Overheat

:

Line mode: Switch to Bypass; Backup Mode: Shutdown UPS immediately
Battery low

:

Alarm and switch off
EPO (optional)

:

Shutdown UPS immediately
Audible & visual alarm

:

Line failure; Battery Low, Overload, System Fault
Communication interface

:

USB (or RS232), SNMP card / relay card (optional)
ENVIRONMENTAL

:

Operating temperature

:

0 ~ 40ºC
Storage temperature

:

-25 ~ 55ºC
Humidity range

:

20 ~ 90% (non-condensing)
Altitude

:

<1500m
Noise level

:

<50dB at 1meter
STANDARDS

:

Safety

:

IEC/EN62040-1, IEC/EN60950-1
EMC

:

IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8
BATTERY PACK for 6~10kVA

:

Voltage

:

+/-120Vdc
Type & number

:

20 x 12V/7Ah SLA Battery
Dimensions W x H x D

:

440 x 130 x 720mm (3U)
Net weight

:

57Kg
Gross weight

:

62Kg

Key Features

Reliable Power for Various Applications

Auto Charging at Off Mode

Auto-Restart Function

Cost Effective Solution