UPS Online Sinewave

RN1102C11

10.000VA / 9000W | 120 ~ 276Vac

ICA UPS RN 1102 C11 Capacity 10.000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Key Features

Reliable Power for Various Applications

Auto Charging at Off Mode

Auto-Restart Function

Cost Effective Solution

Specification

Capacity

:

10.000VA / 9.000W
AC Input Voltage

:

120 ~ 276Vac
Inverter Output Voltage

:

220 / 230 / 240V
Inverter Output Waveform

:

Inverter Output Efficiency

:

≥90%
Transfer Time

:

0ms
Dimension (L x W x H)

:

790 x 580 x 290mm
Net Weight

:

30Kg
INPUT

:

Input mode

:

Single phase + Ground
Power factor

:

≥0.99
Rating voltage

:

220 / 230 / 240Vac (can be set)
Rating frequency

:

50 / 60Hz (auto sensing)
Frequency range

:

45 ~ 55Hz / 54 ~ 66Hz
Bypass voltage range

:

220Vac max : 10%, 15%, 20% or 25%, default : 25%
230Vac max : 10%, 15% or 20%, default +20%
240Vac max : +10% or 15%, default +15% Min : 20%, 30% or 45%, default 45%
Bypass frequency range

:

±1%, ±2%, ±4%, ±5%, ±10%
THDI

:

≤3% (100% liner load, input THDV ≤1%) ; ≤5% (100% liner load, input THDV ≤1%)
BATTERY

:

Battery number

:

16 / 18 / 20pcs (can be set)
Battery type

:

VRLA
Charge model

:

Boost charge or float charge auto switch
Charge time

:

Boost charge up to 20Hr (Max)
Charge current (A)

:

1A (S) / 10A (H)
OUTPUT

:

Output Type

:

Single phase + Ground
Ouput precision

:

1.0%
Voltage distortion (THD)

:

≤2% at 100% liner load; ≤5% at 100% non-liner load
Frequency precision

:

±0.1%
Rating frequency

:

50 / 60Hz
Frequency track speed

:

1 Hz/s
Overload

:

105% ~ 110%, 1 Hr; 110% ~ 125%, 10min; 125% ~ 150%, 1min; ≥150% 200ms
Peak Value factor

:

3 : 1
Dynamic respond

:

5.0%; 20ms
DC heft

:

≤500mV
SWITCH

:

Between Inverter mode and Bypass

:

0ms ; Unlock : <15ms (50Hz), <13.33ms (60Hz)
Norse

:

<55dB (1m)
Display

:

LCD + LED
Safety

:

Metting IEC62040-1 GB4943
Max. input voltage

:

320Vac, 1Hr
EMI

:

Conduction : IEC 62040-2; Radiation : IEC 62040-2; Harmonics : IEC 62040-2
EMS

:

IEC 62040-2
MTBF

:

250.000Hr 1 + 1 400.000Hr
MTTR

:

30min
Isolation resistance

:

>2M Ω (500Vdc)
Isolation intension

:

2820Vdc, <3.5mA, 1 min
Surge

:

Meeting IEC60664-1 1.2/50uS + 8/20uS 6Kv/3kA
Protection

:

IP20
Parallel circuimfluence

:

1 + 1 ≤ 8%, N + 1 ≤ 3%
Parallel equal current

:

1 + 1 ≤ 8%, N + 1 ≤ 10%

Key Features

Reliable Power for Various Applications

Auto Charging at Off Mode

Auto-Restart Function

Cost Effective Solution

Document & Download

No data was found