UPS Online Sinewave

SE4102C33

40.000VA / 36.000W | 208 ~ 478Vac

ICA UPS SE4102C33 Capacity 40.000 VA, inverter only works when the AC input voltage is low or loss. When the AC input voltage is in normal condition, ICA UPS will stabilize and filter the AC input voltage and supply a clean and stable AC voltage to the ICA UPS output and charge the battery. When the AC input voltage is low or loss, inverter will replace it and supply a stable AC voltage within a very short transfer time.

Key Features

Reliable Power for Various Applications

Auto Charging at Off Mode

Auto-Restart Function

Cost Effective Solution

Specification

Capacity

:

40000VA / 36000W
AC Input Voltage

:

208 ~ 478Vac
Inverter Output Voltage

:

380 / 400 / 415Vac (3Ph+N+PE)
Inverter Output Waveform

:

Inverter Output Efficiency

:

94.5%
Transfer Time

:

Utility to Battery: 0ms; Utility to Bypass: 0ms
Dimension (L x W x H)

:

860 x 255 x 860mm
Net Weight

:

71Kg
Nominal Voltage

:

380 / 400 / 415Vac (3Ph+N+PE)
Operating Frequency Range

:

45~55Hz / 54~66Hz (auto sensing)
Power Factor

:

≥0.99
Bypass Voltage Range

:

380Vac Max. voltage: 25% (optional +10%, +15%, +20%)
400Vac Max. voltage: +20% (optional +10%, +15%)
415Vac Max. voltage: +15% (optional +10%)
Min. voltage: -45% (optional -20%, -30%)
Bypass Frequency Range

:

Frequency synchronize tracing range: ±10%
ECO Range

:

Same as bypass
Harmonic Distortion (THD)

:

≤3% (100% non-linear load)
BATTERY

:

Battery Voltage

:

±240Vdc
Backup Time

:

6 ~ 10 minutes
Backup Configuration

:

External
OUTPUT

:

Power Factor

:

0.9
Voltage Regulation

:

±1%
Frequency Line Mode

:

±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency (optional)
Frequency Bat. Mode

:

50/60 (±0.1)Hz
Crest Factor

:

3:1
Harmonic Distortion (THD)

:

≤2% with linear load, ≤5% with non-linear load
SYSTEM FEATURES

:

Overload

:

Load ≤100%: last 60min; ≤125%: last 10min; ≤150%: last 1min; ≥150% change to bypass
Short Circuit

:

Hold Whole System
Communication

:

USB, Rs232, Rs485, Parallel port, REPO port, Coupler dry contact, Intelligent slot, SNMP card (optional), Relay card (optional)
ENVIRONMENTAL

:

Operating Temperature

:

0 ~ 40ºC
Storage Temperature

:

-25 ~ 55ºC (No battery)
Humidity Range

:

0 ~ 95% (Non-condesing)
Altitude

:

1500m, lower the rated power for use
Noise Level

:

<58dB
PHYSICAL UPS Without External Battery (UPS Only)
STANDARDS

:

Safety

:

IEC/EN62040-1, IEC/EN60950-1
EMC

:

IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8

Key Features

Reliable Power for Various Applications

Auto Charging at Off Mode

Auto-Restart Function

Cost Effective Solution

Document & Download

No data was found